Eaton Electrical Powerware 9315 User Manual

Page 72

Advertising
background image

Product Specifications

9-2

EATON Powerware

®

9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

Table 9-3. System Output

Rectifier/Charger Capacity

125%

DC Filtering

Ripple voltage less than 0.5% peak to peak

UPS Output Capacity

100% rated current

Output Voltage Regulation

1% (10% to 100% load)

Output Voltage Adjustment

(Nominal +/–5%)

208 Vac nominal, adjustable from 198 Vac to 218 Vac (60 Hz only)

480 Vac nominal, adjustable from 456 Vac to 504 Vac (60 Hz only)

600 Vac nominal, adjustable from 570 Vac to 630 Vac (60 Hz only)

400 Vac nominal, adjustable from 380 Vac to 420 Vac (50/60 Hz)

Output Voltage Harmonic Content

3% max THD, 2% max single (linear load)

Output Voltage Balance

3% for 100% maximum load imbalance

Output Voltage Phase

Displacement

3° for 100% maximum load imbalance

Output Transients

5% for 100% load step or removal

Frequency Regulation

0.01 Hz free running

Synchronous to Bypass

Bypass within voltage limits of +5%, –8% of output setting; bypass within

±0.5 Hz

Frequency Slew Rate

1 Hz per second maximum (adjustable)

Overload Capability

125% for 10 minutes

150% for 10 seconds

Maximum Output Capability

300% peak for 10 cycles without bypass

Table 9-4. Environmental Specifications

Operating Temperature

0 to 40°C without derating. However, operating at or near 40°C will

adversely affect battery life (refer to your battery specifications for more

information). The recommended operating temperature is 25°C.

Operating Altitude

Maximum 1500m (5000 ft) at 40°C without derating

Storage Temperature

–20 to +70°C (prolonged storage above 40°C will cause rapid battery

self-discharge)

Relative Humidity (operating and

storage)

95% maximum noncondensing

Acoustical Noise

65 dBA at a 1m distance

EMI Suppression

Meets FCC Regulation 47, Part 15, Subpart J, for class A devices

Electrostatic Discharge (ESD)

Immunity

Meets IEC 801-2 specifications. Withstands up to 25 kV without damage and

with no disturbance or adverse effect to the critical load.