Eaton Electrical Powerware 9315 User Manual

Page 31

Advertising
background image

Using the Monitor Panel

5-5

EATON Powerware

®

9315 UPS (200–300 kVA) Operation Manual S 164201036 Rev F powerware.com

Ī

Graphics - Displays a real-time graphic representation of the flow of current through

the internal UPS components.

Ī

Setup - Allows you to configure the UPS communication port and set the date and time

for the timestamp.

Figure 5-3 shows the LCD screen as it appears when you first start the UPS. The Meters

menu is displayed in the menu box, with the System option highlighted. In the information

area, the system meters show their current readings.

Uninterruptible Power System

System Normal

Alarm:

None

Notice: None

Meters

System

Load Amps

Events Statistics Graphics Setup

Input

Output

Bypass

Battery

VAB

480

VBC

VCA

KW

379

KVA

399

IA

IB

IC

FREQ

60.0

PF

0.95

V

540

I

000

Meters

480

480

480

480

480

VAB

480

VBC

VCA

480

480

IA

IB

IC

361

361

361

IN

000

VAB

480

VBC

VCA

480

480

FREQ

60.0

KVA

300

KW

240

PF

0.80

Battery

04 MAY 1997

14:23:45

100%

Percent

Figure 5-3. System Meters Screen (Typical for Powerware 9315 300 480/480V UPS)

The Input area shows the phase-to-phase voltage, frequency, and phase current of the

incoming utility, followed by the kVA, KW, and power factor measurements. The output

area shows the same information for the power being output by the UPS.

The Bypass area shows the phase-to-phase voltage of the bypass source. The Battery area

displays the DC voltage (V) and the DC current (I).

Select Load Amps from the Meters menu to see a real-time bar graph of the output

current of the UPS. The graph shows the current for each phase.

Figure 5-4 shows the Load Amps Meters screen.

Advertising