7.3 Examples of Multi UPS configurations

Electrical drawing

Description

" Minimal number

of necessary

UPSs"

2 UPSs of 1000 VA in parallel through a Static Transfer
Switch
1 UPS loaded at 75 %
1 UPS loaded at 0%

1

2 UPSs of 1500 VA and a server with redundant power
supply
Each UPS loaded at 25 %

1

2 UPSs of 1500 VA and a server with redundant power
supply
Each UPS loaded at 60 %

2

2 UPSs of 3000 VA in hot standby configuration
1 UPS loaded at 33 %
1 UPS loaded at 0%

1

2 UPSs 30 KVA parallel/ redundant mode
Each UPS loaded at 40 %

1

2 UPSs 30 KVA parallel/power extension mode
Each UPS loaded at 60 %

2

4 UPSs 100 KVA parallel
(3 power extension + 1 redundant mode)
Each UPS loaded at 70 %

3

8 UPSs 400 KVA parallel
(7 power extension + 1 r redundant mode)
Each UPS loaded at 80 %

7

7.4 Multi-UPS Systems and Event Management

Please refer to the