7.8.4 The action parameters (execute and send email)

The Parameter... buttons let you access following screen:

The action parameters (execute and send email)


The following parameters can be transmitted to actions:

Parameter

Description

/object

Send object name as a parameter

/value

Send object value as a parameter

/message

Send formatted message as a parameter (refer to label file)

/date

Send date in YYYY/MM/DD - HH:MN:SS format

/ldate

Send date in the local format of Network Shutdown Module host

/card_proxy Send Network Management Card / Proxy name or IP address
/hostname

Send Network Shutdown Module host name or IP address

7.8.5 Software utilities

The following utilities are supplied to help you to customize your "Execute" actions:

7.8.5.1 Shutdown.bat (Windows Script)

The "shutdown.bat" script lets you customize the system shutdown.

It allows:

z

synchronous (which block whilst running) or asynchronous programs to be run before shutting the system
down.

z

programs to be time delayed. The "

wait.exe

" synchronous utility, distributed by EATON in the Network

Shutdown Module default installation directory (<Program Files\EATON\NetworkShutdownModule), is
used.

z

programs with specific rights to be run.

Using eatonRunAs.exe

(Windows NT/2000/2003/XP).