Network Shutdown Module V3 – User Manual - 34 003 934 XU / AE

Page 44/65

Example

A UPS protects 3 machines hosting a Network Shutdown Module. Machine 3 is programmed to shut down
before the others to take some of the load off the UPS.

Machine 1 Machine 2 Machine 3

Shutdown timer

None

None

100 sec

Shutdown duration

120 sec

180 sec

60 sec

The main output shutdown duration is equal to 180 sec. It is the shutdown duration of the machine 2
(maximum of all the shutdown duration).

Shutdown criteria reached

Maximum shutdown
duration

Utility Failure

Shutdown
duration 2

Shutdown
duration 3

Utility

UPS output

Machine 2 on
main outlet group

Machine 3 on
main outlet group

Shutdown

timer

Utility restored

UPS Shut Off

Autonomy

30%

Machine 1 on
main outlet group

Shutdown duration 1