PD8 Series Explosion-Proof Instrument Supplemental Manual

8

Digital Inputs & Outputs

Note: PD8 Series P

RO

V

U

integrated functionality models only.

See notices and warnings on page 18.

CHANNELS

4 digital inputs & 4 digital outputs per module

SYSTEM

One expansion module may be added for a total of 8 in-
puts & 8 outputs

Note: The jumper located between the RJ45 connectors
must be removed on the expansion module.

DIGITAL INPUT
LOGIC HIGH

3 to 5 VDC

DIGITAL INPUT
LOGIC LOW

0 to 1.25 VDC

DIGITAL OUTPUT
LOGIC HIGH

3.1 to 3.3 VDC

DIGITAL OUTPUT
LOGIC LOW

0 to 0.4 VDC

SOURCE
CURRENT

10 mA maximum output current

SINK
CURRENT

1.5 mA minimum input current

+5 V
TERMINAL

To be used as pull-up for digital inputs only.
Connect normally open pushbuttons across +5 V & DI 1-4.

WARNING

DO NOT use +5 V terminal (pin 1) to
power external devices.

External Switch Contacts

PD8-765 Series Trident X2 integrated functionality models only. See Vigilante II
Instruction Manual for information on PD8-154 and PD8-158 Series external switch
contact specifications.

Open State

+5 VDC open contact on switch input terminals

Closed State

Closed contact switch input terminal to common/ground,
active low 0 to 0.4 VDC, or open collector transistor acti-
vated input

Advertising