Ind. LuNAR RK200DTG3 Installation
Guide
15
Selectors and Jumpers
RC/SET
INPUT
Used to determine the polarity of the external inputs.
12V: 12v has to be connected in order activate the function.
GND or N.C. has no influence on the RC/SET status.
(see Relay mode DIP switches configuration)
0V: The GND has to be connected in order to activate the
function.
12v or N.C. has no influence on the RC/SET status.
(see Relay mode DIP switches configuration)
EOL
RESISTORS
JUMPERS
FAULT/AM
EOL
JUMPERS
12K
No
Resistor
(Default)
The jumpers are used when connecting the
detector to a DEOL or TEOL Zone. The jumpers
allow the selection of TAMPER, ALARM E.O.L
resistors (1K, 2.2K, 4.7K, 5.6K or 6.8K), according
to the control panel settings. An additional double
jumper allows the connection of 12K FAULT/AM
E.O.L resistor (see EOL Resistors Schematic).
Follow the terminal block connection diagram
when connecting the detector to a Double/Triple
End Of Line (DEOL/TEOL) Zone