H4 ENERGY & PROCESS ASSESSMENT PROTOCOL

Heat transfer through the building envelope due to warmer outside air

■

Infi ltration due to wind and a stack effect (gravity forces)

■

Ventilation airfl ow rate

■

Internal factors:

Industrial processes such as machining, welding, heat treatment, etc.

■

Electrical motors

■

Process equipment with a high surface temperature

■

Steam or hot water pipes, hot water tanks, etc.

■

Lighting

■

People

■

Computers, vending machines.

■

H.5.2 Cooling Load of HVAC System

If cooling is provided by HVAC system with a cooling coil, cooling load is cal-
culated using the following equation:

Q

cool

=

␳

* q

vent

* (h

s

−

h

out

)

where

Q

cool

= cooling load of ventilation, kW

␳

= air density, kg/m

3

q

vent

= ventilation

airfl ow rate, m

3

/s

h

s

= supply air enthalpy, kJ/kg

h

out

= outside air enthalpy, kJ/kg

H.5.3 Heating Energy Consumption

Generally, the heating energy consumption of a building can be calculated
using the following equation:

Q

=

(Q

loss

+

Q

inf

+

Q

vent

+

Q

hv

−

Q

int. load

/

␩

where

Q

= heating energy consumption, kWh

Q

loss

= losses of heat through the building envelope, kWh

Q

inf

= heat losses due to infi ltration, kWh