Retrotec USACE User Manual

Page 380

Advertising
background image

J4 ENERGY & PROCESS ASSESSMENT PROTOCOL

Temp
scale

kW/ton
scale

Condenser water return temperature

Condenser water supply temperature

Chiller kW per ton of cooling

Chilled water supply temperature

Chilled water return
temperature

Figure J2. Example of Load-Based Optimization System (LOBOS) reset strategies in operation.

This test was run to see what effects changing the condenser water tem-

■

perature setpoint would have on VFD chiller system effi ciency.
The red line is the condenser water temperature with a system using

■

the Load-Based Optimization System (LOBOS) control system, which
determines less wasteful, more effi cient operating points for the heat-
ing, ventilating, and air-conditioning (HVAC) system based on the
actual cooling loads of the facility.
The blue line is the chiller effi ciency in kW per ton.

■

The green line is the chilled water supply temperature.

■

The test shown in the trend log screenshot shows that the chiller

■

energy effi ciency is running at approximately 0.33 kW per ton prior to
the start of the test.
This is excellent effi ciency, as most chillers installed today operate

■

between 0.60 and 1.5 kW per ton of cooling.
With LOBOS, the condenser water temperature is running at approxi-

■

mately 20 °C (68 °F), while the chilled water temperature is running at
approximately 10 °C (50 °F).
We manually raised the condenser water setpoint to 26.7 °C (80 °F)

■

from the automatically controlled setpoint of 68 °F to determine what
effect a “normal” operating strategy would have on chiller system per-
formance. Many facilities routinely operate their condenser water sys-
tems at between 26.7 and 29.4 °C (80 and 85 °F), the typical “design”
points for chillers when they leave the chiller factory.
As can be seen, the chiller effi ciency was made dramatically worse

■

when the CHWS temperature was raised by 11.1 °C (12 °F), increas-
ing from 0.33 kW per ton to 0.45 kW per ton, using 36% more energy

Advertising