Amprobe IR-750 Infrared-Thermometer User Manual

Page 24

Advertising
background image

19

Measuring Grille, Register, or Diffuser Discharge Temperature

1. Press SET and then press

/

to select relatively high emissivity.

2. Aim the Thermometer at the discharge air grille, register, or diffuser.

3. Measure discharge temperature.

4. Release trigger to freeze the temperature reading for 8 seconds and

record this temperature.

5. Grille, register, or diffuser temperature should be equivalent to discharge

temperature at the air handler.

Checking for Blockage in Air-To-Air Evaporator or Condensers

1. Remove panels to gain access to coil return bends or hairpins.

2. Press SET and then press

/

to select relatively high emissivity for

copper tube.

3. Start the refrigeration system.

4. Aim the Thermometer at coil turn bends/hairpins.

5. Start recording temperature.

6. Take temperature of each return bend/hairpin.

• All evaporator return bends/hairpins should be at or slightly above

evaporator saturation temperature from the pressure/temperature chart.

• All condenser return bend/hairpins should be at or slightly less than

condenser saturation temperature.

• If a group of return bends/hairpins do not conform to expected

temperatures, that indicates a blocked or restricted distributor or
distributor tube.