Parameter

Description

DataInput,
arraynamename

both AN-X modules

ClxName

ClxName is used in the address part of the aliases
for elements that are unique for each AN-X, such
as diagnostics. It is usually set equal to the
Ethernet host name.

ClxPrefix

The ClxPrefix is used in the alias name for I/O
data. It should be the same for both AN-X
modules in a redundant application.

RedundEna

Include a line with the RedundEna parameter, followed by a comma and
a unique name for the AN-X at the start of the ControlLogix
configuration file.

RedundPrefix

AN-X uses the RedundPrefix when it generates aliases for elements that
are unique to each AN-X module, such as diagnostics.

RedundCtl

RedundCtl consists of a single 16-bit word. Only bit 0 is used. To
enable an AN-X to act as the scanner, set bit 0 to 1. To disable the
AN-X, set bit 0 to 0.

Map RedundCtl to the output data for the connection to slot 0 in each
AN-X. If the configuration file contains RedundEna, you must map
RedundCtl.

ScanSts

ScanSts is an array of 5 INTs that contain information about the current
operation of the Modicon S908 network scan.

Offset

Description

0

Scan state

0=idle, no packets being received from the S908 network

1=monitor, another master is active

2=scanning

3=scan halted, was actively scanning but the enable bit has
been turned off

1

Scan counter, increments at the start of each S908 network
scan