AN-X-MOD (Master)

November 2011

Offset

Description

2

Init counter, increments whenever a drop on the S908
network is reinitialized

3

current S908 network update time

4

maximum S908 network update time

Map ScanSts to input data for any connection.

By default, when you perform an autoconfiguration and create a
ControlLogix configuration, AN-X maps the ScanSts array to the
connection to slot 15, but comments out the mapping.

LongInput

800 series drops send inputs only when the inputs change. In redundant
applications with 800 series drops, include the LongInput parameter in
the ControlLogix configuration file to ensure that the backup has the
latest inputs.

Aliases

The AN-X-MOD (Master) creates aliases that can be imported into
RSLogix 5000.

Item

Alias name prefix

Base tag

Unique elements,
such as diagnostics

RedundPrefix

ClxName

I/O inputs

ClxPrefix

DataInput name, if
present

I/O outputs

ClxPrefix

DataOutput name, if
present

Switchover

When you turn on the RedundCtl bit for an AN-X-MOD (Master)
module, it waits for 10 ms of silence on the network before it starts
scanning as master.

WARNING!!! If the RedundCtl bits on both AN-X modules are on, only
one acts as master. However, if the bits are set on both AN-X modules
and the current master is disconnected from the S908 network, even for a
very short period, the backup takes over. If the module that was
disconnected comes back online, both modules will be master on the
S908 network. YOUR APPLICATION MUST CHECK FOR THE
DUPLICATE MASTER CONDITION AND TAKE APPROPRIATE
ACTION!