Command block list – ProSoft Technology 5201-DFNT-104S User Manual
Page 111

Reference 104S
v2
♦ ProLinx Gateway
Protocol Manual
(Firmware v2.xx)
ProSoft Technology, Inc.
Page 111 of 157
March 19, 2010
Once the command response block is processed, the response data will be
copied to the ProLinx database with the following structure. The command
response block will be copied starting at the database address given by the
configuration parameter DB Output Window Start:
Word Offset
Description
0
Block ID2 - Command Request With Response
1
Block ID1 - Command Request Without Response
2 to 98
Command Response Data
99
Block ID2 - Command Request With Response
The remote node must therefore read this block from the ProLinx gateway to
retrieve the command block response.
5.2.3 Command Block List
The following command blocks are supported by the gateway:
Block Range
Mode
Direction
Description
100 and 101
Command Request
without Response
Node to ProLinx Event Data
200 and 201
Command Request
without Response
Node to ProLinx Set Time
200 and 201
Command Request
with Response
ProLinx to Node Get Time
202 and 203
Command Request
with Response
ProLinx to Node Get Event Buffer Counts