2.1.2 [IEC-870-5-104]
This section provides information required to configure a server application with
the gateway. Most entries contained within this section are self explanatory.
Use IP List
N
O
(0) or Y
ES
(1)
This parameter specifies if the IP address of the host connected to the system
will be validated. If the parameter is set to N
O
(0), any host may connect to the
unit. If the parameter is set to Y
ES
(1), only hosts in the IP list will be permitted to
connect to the unit.
Override StartDT
N
O
(0) or Y
ES
(1)
This parameter is used when testing the gateway with a simulator or with a Client
unit that does not meet the IEC 60870-5-104 specification. After the Clinet
connects to the gateway, it will send a STARTDT.ACT U-format message to the
gateway to permit the gateway to start sending data. If the Client does not
support this requirement, set the parameter to Y
ES
(1). Set the parameter to N
O
(0) if the Client sends the STARTDT.ACT message.
Note: This parameter must be set to N
O
(0) if you wish to use the redundant Clients feature.
March 19, 2010