IEC-60870-5-104 (104S) Protocol Implementation

104S v2 ♦ ProLinx Gateway

Protocol Manual

(Firmware v2.xx)


ProSoft Technology, Inc.

Page 55 of 157

Freeze Start Type
The Freeze Start Type parameter will define when the gateway starts sending
the M_IT messages.

Example I - Freeze Start Type

If the gateway powers up with the following date and time clock:

03/25/2004 18:07:42

If you configure the Interval For Freeze parameter as follows:

The gateway would send the counter messages every 15 seconds. The gateway
would start sending the messages depending on the Freeze Start Type
parameter as follows:

Freeze Start Type

Time to Start Sending Messages

D 03/26/2004

00:00:00

H 03/25/2004

19:00:00

M 03/25/2004

18:08:00