Monitor data transfer – ProSoft Technology 5201-DFNT-104S User Manual

Page 50

Advertising
background image

104S v2 ♦ ProLinx Gateway

IEC-60870-5-104 (104S) Protocol Implementation

(Firmware v2.xx)

Protocol Manual


Page 50 of 157

ProSoft Technology, Inc.

March 19, 2010

3.3.1 Monitor Data Transfer

Typically, you should properly configure the group code for each monitor point to
define how the master will poll for the point. The group codes are defined as
follows:

The Group parameter is defined as follows:

Group Code

Description

0x00000001

Interrogated by general interrogation (station or global)

0x00000002

Interrogated by group 1 interrogation

0x00000004

Interrogated by group 2 interrogation

0x00000008

Interrogated by group 3 interrogation

0x00000010

Interrogated by group 4 interrogation

0x00000020

Interrogated by group 5 interrogation

0x00000040

Interrogated by group 6 interrogation

0x00000080

Interrogated by group 7 interrogation

0x00000100

Interrogated by group 8 interrogation

0x00000200

Interrogated by group 9 interrogation

0x00000400

Interrogated by group 10 interrogation

0x00000800

Interrogated by group 11 interrogation

0x00001000

Interrogated by group 12 interrogation

0x00002000

Interrogated by group 13 interrogation

0x00004000

Interrogated by group 14 interrogation

0x00008000

Interrogated by group 15 interrogation

0x00010000

Interrogated by group 16 interrogation

0x00020000

Interrogated by general counter request

0x00040000

Interrogated by group 1 counter request

0x00080000

Interrogated by group 2 counter request

0x00100000

Interrogated by group 3 counter request

0x00200000

Interrogated by group 4 counter request

0x40000000

Disable event scanning of this point

0x80000000

Periodic/cyclic data returned from unit

Advertising