Iec-870-5-104 database, Short pulse time, Long pulse time – ProSoft Technology 5201-DFNT-104S User Manual

Page 25

Advertising
background image

Configure the Gateway

104S v2 ♦ ProLinx Gateway

Protocol Manual

(Firmware v2.xx)


ProSoft Technology, Inc.

Page 25 of 157

2.1.3 [IEC-870-5-104 Database]

This section describes parameters in the [IEC-870-5-104 Database] section.

Short Pulse Time

0 to 2,147,483,647 (2 raised to the power of 31) milliseconds

This parameter defines the number of milliseconds to keep an IEC Command
Point set ON, HIGH, equal to one (1), before returning the point to OFF, LOW,
equal to zero (0), whenever a pulse point command is sent by the Client and the
default value of the Default Command Qualifier parameter is set to S

HORT

.

Long Pulse Time

0 to 2,147,483,647 (2 raised to the power of 31) milliseconds

This parameter defines the number of milliseconds to keep an IEC Command
Point set ON, HIGH, equal to one (1), before returning the point to OFF, LOW,
equal to zero (0), whenever a pulse point command is sent by the Client and the
default value of the Default Command Qualifier parameter is set to L

ONG

.

March 19, 2010

Advertising