Wiring

CAUTION

• Be sure to wire correctly and securely.

Failure to observe this caution may result in motor overrun, injury, or
malfunction.

• Do not connect a commercial power supply to the U, V, or W ser-

vomotor connection terminals.

Failure to observe this caution may result in injury or fire.

• Securely connect the power supply terminal screws and servo-

motor connection terminal screws.

Failure to observe this caution may result in fire.

• Do not bundle or run the main circuit cables and input/output sig-

nal lines or the encoder cables together in the same duct. Keep
power and signal lines separated by at least 30 cm.

• Use twisted-pair shielded wires or multi-core twisted pair

shielded wires for input/output signal lines and the encoder
cables.

The maximum length is 3 m for input/output signal lines and 20 m for
encoder cables.

• Do not touch the power terminals for 5 minutes after turning

power OFF because high voltage may still remain in the SERVO-
PACK.

Make sure the charge indicator is out first before wiring or starting an
inspection.

• Observe the following precautions when wiring main circuit termi-

nal blocks.

• If the main circuit terminal is the connector, remove the connector

from the SERVOPACK prior to wiring.

• Insert only one wire per insertion slot on the terminal block and the

connector.

• Make sure that the core wire is not electrically shorted to adjacent core

wires.