Framing & Clearances

Several options are available to you when choosing a loca-

tion for your fireplace. This fireplace may be used as a room

divider, installed along a wall, across a corner or used in an

exterior chase. See Figure 6.1
Locating the fireplace in a basement, near frequently opened

doors, central heat outlets or returns, or other locations of

considerable air movement can affect the performance and

cause intermittent smoke spillage from the front of the fire-

place when no outside air is used. Outside air must be used

for combustion. The Constitution comes equipped with an

outside air inlet to feed combustion air from outside the

home, along with an outside air termination cap. Consider-

ation should be given to these factors before deciding on a

location. See Sections 4 and 5.

NOTICE:

• Illustrations and photos reflect typical installations and

are FOR DESIgN PURPOSES ONLY.

• Illustrations/diagrams are not drawn to scale.

• Actual installation/appearance may vary due to

individual design preference.

• Hearth & Home Technologies reserves the right to alter

its products.

D

C

A

E

F

A

H

G

B

A

B

B

A

I

In an exterior chase

or projecting into a

garage

Across a corner

Along a wall

As a

room

divider

24 in.

(610mm)

24 in.

(610mm)

24 in.

(610mm)

48 in.

(1219mm)

Model:

Constitution

(Dimensions for

finished walls)

A

B

C

D

E

F

G

H

I

in.

41-7/8 16 89-1/2 63-5/16 22-7/16 44-3/4 14-1/16 55-15/16 50-7/8

mm

1063 406

2273

1608

570

1137

357

1421

1292

Figure 6.1 Fireplace Locations

NOTICE:

measurements are FRAmING dimensions only and do not include drywall either in the cavity or on

the interior walls.

NOTICE: In addition to these framing dimensions, also

reference the following sections

• Clearances (Section 6.B)

NOTICE:

A minimum 1 in. air clearance must be maintained

at the back and to the sides of the fireplace as-

sembly.
Chimney sections at any level require a 2 in. mini-

mum air space clearance between the framing

and chimney sections.