B. Clearances

WARNING! Risk of Fire! You must comply with all minimum air space clearances to combustibles as specified in Fig-

ure 6.2.

DO NOT pack required air spaces with insulation or other materials.Framing or finishing material used on the

front of, or in front of, the appliance closer than the minimums listed.must be constucted entirely of non-combustible mate-

rials (i.e., steel studs, concrete boaed, etc.). Failure to comply may cause fire.

2 in. (51 mm) min.

Attic

Insulation

Shield

Ceiling Firestop

(ceiling)

(roof)

(attic)

(ceiling)

Ceiling Firestop

Offset/Return with

hanger straps

Storm Collar

Roof Flashing

2 in. (51 mm) min.

2 in. min.

(51 mm)

Must have 2 in. (51 mm)

minimum clearance

to header

2 in. (51 mm) min.

2 in. (51 mm) min.

2 in. (51 mm) min.

2 in. (51 mm) min.

1 in. (25mm) to side of appliance

(except at nailing flanges where it is 1/2 in. [13 mm])

1 in. (25 mm) to back

of appliance

0 in.

to floor

0 in. to level

of standoffs

NOTICE: Chimney air kit is not shown, but is required.

Figure 6.2 Clearances to Combustible Materials