E. hearth extension – Heat & Glo Fireplace Heat & Glo Gas Fireplace ESC-42ST User Manual

Page 22

Advertising
background image

Heat & Glo • ESC-42ST • 2146-900 Rev. Q • 4/13

22

E. Hearth Extension

WARNING! Risk of Fire! Hearth extension required to
protect combustible fl oors in front of appliance.

WARNING! Risk of Fire! DO NOT block ventilation
slots.
A minimum 1/4 in. space between the bottom of
hearth refractory and top of fi eld installed hearth exten-
sion (marble, tile, granite, etc) is required across full width
of fi replace.

If the appliance is to be placed directly on the fl oor, the
non-combustible hearth material will be limited to 3/4 in.
thick, including the fl oor adhesive. If the hearth mate-
rial will exceed 3/4 in. thick, the appliance will need to
be shimmed from the fl oor appropriately to maintain 1/4
in. minimum space between the fl oor hearth and hearth
refractory.

The base of the fi replace may sit on a combustible surface.
The area in front of the fi replace must be protected by a
noncombustible hearth extension, unless the fi replace is
raised a minimum of three inches above the combustible
fl oor or hearth. See Figures 5.7, 5.8 and 5.10.

Figure 5.9 Non-Combustible Zone

Figure 5.10 Non-Combustible Hearth Extension Minimum

Dimensions (Fireplace Positioned on Combustible
Surface)

A

B

in.

60-1/4

12

mm

1530

305

Figure 5.7 Fireplace Positioned on Combustible Surface

WOOD OR OTHER

COMBUSTIBLE

FLOOR OR PLATFORM

3-3/4 IN.

COMBUSTIBLE MATERIAL

1 IN. MAX THICKNESS

ALLOWED UNDER

FIREPLACE

BOTTOM OF FIREPLACE

3 IN.
MIN.

MINIMUM

1/4 INCH SPACE

REQUIRED

Figure 5.8 Fireplace Raised A Minimum of 3 Inches Above

Combustible Surface

3-1/2 IN.

NO COMBUSTIBLES

IN THIS AREA

1/2 IN. BUILDING MATERIAL

(MAY BE COMBUSTIBLE)

COMBUSTIBLE

FRAMING

4 IN.

FACTORY-

SUPPLIED 1/2 IN.

NON-

COMBUSTIBLE

BOARD

39 IN.

23 IN.

A

B

WOOD OR OTHER

COMBUSTIBLE FLOOR

OR PLATFORM

MARBLE, GRANITE, TILE OR

OTHER NON-COMBUSTIBLE

HEARTH EXTENSION

3/4 IN. MAX

12 IN.

HEARTH

REFRACTORY

BOTTOM OF

FIREPLACE

NON-COMBUSTIBLE

MATERIAL ON SIDES

(PROFILE VIEW)

MINIMUM

1/4 INCH SPACE

REQUIRED