Heat & Glo Fireplace Heat & Glo Gas Fireplace ESC-42ST User Manual

Page 37

Advertising
background image

Heat & Glo • ESC-42ST • 2146-900 Rev. Q • 4/13

37

B. Assemble Slip Sections

• Slide the inner fl ue of the slip section into the inner fl ue of

the pipe section and the outer fl ue of the slip section over
the outer fl ue of the pipe section. See Figure 10.6.

• Slide together to the desired length.

Figure 10.6 Slip Section Pilot Holes

Figure 10.7 Screws into Slip Section

Pilot hole

Pilot hole

• Continue adding pipe as necessary following instructions

in “Assembling Pipe Sections.”

NOTICE: If slip section is too long, the inner and outer fl ues
of the slip section can be cut to the desired length.

• Maintain a 1-1/2 in. (38 mm) overlap between the slip

section and the pipe section.

• Secure the pipe and slip section with two screws no

longer than 1/2 in. (13 mm), using the pilot holes in the
slip section. See Figure 10.7.

120º

Figure 10.8 Securing Vertical Pipe Sections

120º

Figure 10.9 Securing Horizontal Pipe Sections

C. Secure the Vent Sections

• Vertical runs originating off the top of the appliance, with

no offsets, must be supported every 8 ft. (2.44 m) after
the maximum allowed 25 ft. (7.62 m) of unsupported rise.

• Vertical runs originating off the rear of the appliance, or

after any elbow, must be supported every 8 ft. (2.44 m).

• Horizontal runs must be supported every 5 feet (1.52

m).

• Vent supports or plumbers strap (spaced 120º apart)

may be used to support vent sections. See Figures 10.8
and 10.9.

• Wall shield fi restops may be used to provide horizontal

support to vent sections.

• SLP ceiling fi restops have tabs that may be used to

provide vertical support.

WARNING! Risk of Fire, Explosion or Asphyxiation!
Improper support may allow vent to sag and separate.
Use vent run supports and connect vent sections per in-
stallation instructions. DO NOT allow vent to sag below
connection point to appliance.

Advertising