Top vent - horizontal termination - (continued), Three elbows h – Heat & Glo Fireplace Heat & Glo Gas Fireplace ESC-42ST User Manual

Page 28

Advertising
background image

Heat & Glo • ESC-42ST • 2146-900 Rev. Q • 4/13

28

1. Top Vent - Horizontal Termination - (continued)

Figure 7.5

Three Elbows

H

1

V

2

H

2

V

1

V

1

H

1

V

2

H

2

2 ft

610 mm

7 in

178 mm

*

H

2

Max = 2 X V

2

3 ft

914 mm

2 ft

610 mm

*

H

2

Max = 2 X V

2

4 ft

1.2 m

4 ft

1.2 m

*

H

2

Max = 2 X V

2

5 ft

1.5 m

9 ft

2.7 m

*

H

2

Max = 2 X V

2

6 ft

1.8 m

12 ft

3.7 m

*

H

2

Max = 2 X V

2

7 ft

2.1 m

14 ft

4.3 m

*

H

2

Max = 2 X V

2

10 ft

3.0 m

20 ft

6.1 m

*

H

2

Max = 2 X V

2

V

1

+ H

1

must be adhered to.

* V

2

has no specifi c restrictions EXCEPT,

H

t max

= 2 x V

t

and V

total

+ H

total

cannot exceed 60 ft Maximum

Note: Flue restrictor is permit-
ted ONLY on 30 ft. minimum
vertical runs with no elbows.

Note: Must have a 24 inches minimum
vertical vent before attaching any
elbow to the appliance.