The default address as programmed at the factory is 01. If a different address is required, it may be

changed using either RS-232 or 485. After making the proper serial connections, use the command *00X
to read the default address. Use *00Xdd, where dd = the new address. If the old address is known, use

DDXdd, where DD is the old address and dd is the new address. See the section on "Serial

Communication: Commands" for more on command structure.
All commands listed in Appendix B are available for RS-485 use by inserting an asterisk and the unit's

address in front of the command.
Ex) Set the units of measure on channel two (2) to %.

*10UM203Cr

The command, *00XCr can be used to poll the unit for its current address setting using either RS-232 or

RS-485.

10.5. SELECTING THE ANALOG SIGNAL LEVEL

The

POWER

POD

-400

is capable of 0 to 5 V, 0 to 10 V or 4 to 20 mA operation. Each level is user

selectable. The following diagram applies no matter which level of operation is chosen.


From

SETUP/CAL

Menu


10.5.1. Zero to Five Volt Operation

While in the SETUP/CAL menu, select ANALOG by pressing the number 4 key and the ENTER key.

From the ANALOG SIGNAL menu, choose 0V – 5V by pressing the number 1 key and pressing the

ENTER key. The normal display returns with 0 volts intended to correspond to 0% signal and 5 volts

intended to correspond to the 100% signal. Calibration may be required.

10.5.2. Zero to Ten Volt Operation

While in the SETUP/CAL menu, select ANALOG by pressing the number 4 key and the ENTER key.

From the ANALOG SIGNAL menu, choose 0V – 10V by pressing the number 2 key and pressing the
ENTER key. The normal display returns with 0 volts intended to correspond to 0% signal and 10 volts

intended to correspond to the 100% signal. Calibration may be required.

10.5.3. Four to Twenty Milliamp Operation

While in the SETUP/CAL menu, select ANLG by pressing the number 4 key and the ENTER key.
From the ANALOG SIGNAL menu, choose 4mA – 20 mA operation by pressing the number 3

key and pressing ENTER. The normal display returns with 4 milliamps intended to correspond to
0% signal and 20 milliamps intended to correspond to the 100% signal. Calibration may be
required.