Creating a zoning plan

6

For more than 8 temperature zones or 24 actuators:

►

Determine the number of additional storey controllers required using
the following table:

Temperature
zones (maximum)

Actuators
(maximum)

No. of
storey controllers

8

24

1

16

48

2

24

72

3

The example at the end of this section shows zone divisions
with corresponding zoning plan.

Filling out zoning plan

►

Copy the sample zoning plan (see Appendix, Page 50) (archive it).

►

Enter the type and installation location of the respective actuator in
each temperature zone.

►

Assign a setpoint adjuster to each temperature zone.

►

Assign room names if necessary.

►

Hand over the zoning plan to the customer after installation.