CHAPTER5 OPERATING

14

Profidrive Status Word (ZSW):
The status word indicates the status of the inverter (Inverter -> PLC).

Status word

Bit

Value

Meaning

Remark

1

Ready to switch-on

Control word bit 0=0 and bits 1, 2, 10 are set to 1 (Ready to switch-on
state).

0

0

Not ready to switch-on

Control word bit 0, 1 or 2 (OFF1, OFF2, OFF3) is set to 0, or the inverter
is tripped.

1

Ready for operation

Control word bit 0, 1 and 2 are set to 1. Inverter is not faulted (Ready
state).

1

0

Not ready for operation

Control word bit 0, 1 or 2 (OFF1, OFF2, OFF3) is set to 0, or the inverter
is faulted.

1

Operation enabled

Control word bit 0, 1, 2 and 3 are set to 1. Inverter is not faulted (Enable
operation
state).

2

0

Operation inhibited

Control word bit 0, 1, 2 or 3 (OFF1, OFF2, OFF3, Operation disabled) is
set to 0, or the inverter is faulted.

1

Fault

Inverter is faulted.

3

0

No fault

Inverter is not faulted.

1

ON2

Control word bit1=1.

4

0

OFF2

OFF2 command active. Control word bit1=0 (OFF2 active state).

1

ON3

Control word bit2=1.

5

0

OFF 3

OFF3 command active. Control word bit2=0 (OFF3 active state).

1

Start enable

Control word bit1 or 2 (OFF2, OFF3) is set to 0 or fault has been
acknowledged (Switch-on inhibit state).

6

0

No switch-on inhibit

Control word bit 0=0 and bit10=1 (Not ready to switch-on state).

7

Not used

1

Frequency equal set-point

Actual output frequency does equal frequency set-point.

8

0

Frequency not equal set-
point

Actual output frequency does not equal frequency set-point
(i.e. motor accelerating/decelerating).

1

Bus control

Run command or frequency setting is valid via Profibus.

9

0

Local control

Run command and frequency setting are invalid via Profibus.

1

Frequency within range

Actual output frequency is above or equal to the limit specified by “Arrival
frequency at acceleration/deceleration 1” (C042/C043).

10

0

Frequency out of range

Actual output frequency is below the limit specified by by “Arrival
frequency at acceleration/deceleration 1” (C042/C043).

11

Not used

-

12

-

Mirror of bit 12 in the control word.

13

-

Mirror of bit 13 in the control word.

14,
15

-

Not used

-