CHAPTER5 OPERATING

19

5.5 Profidrive specific parameters

The table below shows which Profidrive specific parameters that are supported by the SJ-PB(T).

Table 5-1 Profidrive parameters

PNU -

Parameter Number

Description

Range

915

Assignment of PZD write word
3-10

Refer to chapter 5.3.3 and 5.4.3 for how to assign PZD
words. Use the parameter cross-reference list in
chapter 5.
Please note: Parameters will be lost when turning
power off unless parameter 971 has been written with
“0->1”.

Parameter range:
1 – 418.
Sub-index range:
1 – 8.

R/W

916

Assignment of PZD read word
3-10

Refer to chapter 5.3.3 and 5.4.2 for how to assign PZD
words. Use the parameter cross-reference list in
chapter 5.
Please note: Parameters will be lost when turning
power off unless parameter 971 has been written with
“0->1”.

Parameter range:
1 – 418.
Sub-index range:
1 – 8.

R/W

918

Profibus-DP slave address

Returns address switch setting.

1-99

R

927

Parameter edit rights

1 – PKW interface enabled. Parameters can be
read/written.
0 – PKW interface disabled, only parameter 927 can
be read/written.

0, 1

R/W

928

Control rights (process data).

1 – Option board will send control word, reference and
will update PZD3-10.
0 – PZD not enabled.

0, 1

R/W

947

Indexed Fault memory

Fault. Codes as described in table 5-2 below.
Sub-index 1 = Not acknowledged fault.
Sub-index 9 = Latest acknowledged fault.
Sub-index 17 = 2

nd

latest acknowledged fault.

Sub-index 25 = 3

rd

latest acknowledged fault.

Sub-index 33 = 4

th

latest acknowledged fault.

Sub-index 41 = 5

th

latest acknowledged fault.

Sub-index 49 = 6

th

latest acknowledged fault.

-

R

963

PROFIBUS-DP baud rate

the baudrate of the Profibus-DP network
0: 12 Mbit/s 1: 6 Mbit/s 2: 3 Mbit/s 3: 1.5 Mbit/s
4: 500 kbit/s 5: 187.5 kbit/s 6: 93.75 kbit/s
7: 45.45 kbit/s 8: 19.2 kbit/s 9: 9.6 kbit/s

0-9

R

964

Device identification

Bit 15 represents the type of inverter, 0 – SJxxx, 1 –
LxxxP. Rest of the word represents the model number.
SJ300 - 0x012C
L300P - 0x812C

012Ch, 812Ch

R

965

Profile version

Returns the Profidrive profile version used in the SJ-PB
implementation

2

R

967

Control Word

Shows the latest received control word in hex format
Refer to chapter 5.3.1 for detailed information about
the control word.

Bit 0-15

R

968

Status Word

Shows the latest status word in hex format
Refer to chapter 5.3.1 for detailed information about
the status word.

Bit 0-15

R

971

Transfer into non-volatile
memory

Please note that it will take approximately 10s for this
process to finish (inverter must be stopped).
0 – No function.
1 – Will save inverter parameters to non-volatile
memory and the Profile specific parameters to FLASH.

0, 1

W