APPENDIX PARAMETER CROSS-REFERENCE LIST

22

Parameter cross-reference list

To be able to read/write parameters via Profibus it is necessary to use a cross-reference list to convert from
Profibus parameters to actual parameter values in the inverter.
Example, if parameter “1st Acceleration time 1” shall be read then parameter number 23 shall be used (if the
keypad is used F002 is used).
The L300P inverter supports a slightly different parameter map; the “L300P” field reflects this. “No” means
that the L300P inverter does not support the parameter, a figure means that the parameter is supported, but
with this maximum value instead.

Code No. Size

Range

Magn.

Contents

L300P

Read/

Write

A020

1

4

0 400.00Hz

*100

1st setting Multispeed frequency 0

R/W

A220

2

4

0 400.00Hz

*100

2nd setting Multispeed frequency 0

R/W

A320

3

4

0 400.00Hz

*100

3rd setting Multispeed frequency 0

No

R/W

A021

4

4

0 400.00Hz

*100

Multispeed frequency 1

R/W

A022

5

4

0 400.00Hz

*100

Multispeed frequency 2

R/W

A023

6

4

0 400.00Hz

*100

Multispeed frequency 3

R/W

A024

7

4

0 400.00Hz

*100

Multispeed frequency 4

R/W

A025

8

4

0 400.00Hz

*100

Multispeed frequency 5

R/W

A026

9

4

0 400.00Hz

*100

Multispeed frequency 6

R/W

A027

10

4

0 400.00Hz

*100

Multispeed frequency 7

R/W

A028

11

4

0 400.00Hz

*100

Multispeed frequency 8

R/W

A029

12

4

0 400.00Hz

*100

Multispeed frequency 9

R/W

A030

13

4

0 400.00Hz

*100

Multispeed frequency 10

R/W

A031

14

4

0 400.00Hz

*100

Multispeed frequency 11

R/W

A032

15

4

0 400.00Hz

*100

Multispeed frequency 12

R/W

A033

16

4

0 400.00Hz

*100

Multispeed frequency 13

R/W

A034

17

4

0 400.00Hz

*100

Multispeed frequency 14

R/W

A035

18

4

0 400.00Hz

*100

Multispeed frequency 15

R/W

A061

19

4

0 400.00Hz

*100

1st Upper limiter frequency

R/WOS

A261

20

4

0 400.00Hz

*100

2nd Upper limiter frequency

R/WOS

A062

21

4

0 400.00Hz

*100

1st Lower limiter frequency

R/WOS

A262

22

4

0 400.00Hz

*100

2nd Lower limiter frequency

R/WOS

F002

23

4

0.01 3600.00s

*100

1st Acceleration time 1

R/W

F202

24

4

0.01 3600.00s

*100

2nd Acceleration time 1

R/W

F302

25

4

0.01 3600.00s

*100

3rd Acceleration time 1

No

R/W

F003

26

4

0.01 3600.00s

*100

1st Deceleration time 1

R/W

F203

27

4

0.01 3600.00s

*100

2nd Deceleration time 1

R/W

F303

28

4

0.01 3600.00s

*100

3rd Deceleration time 1

No

R/W

A092

30

4

0.01 3600.00s

*100

1st Acceleration time 2

R/W

A292

31

4

0.01 3600.00s

*100

2nd Acceleration time 2

R/W

A392

32

4

0.01 3600.00s

*100

3rd Acceleration time 2

No

R/W

A093

33

4

0.01 3600.00s

*100

1st Deceleration time 2

R/W

A293

34

4

0.01 3600.00s

*100

2nd Deceleration time 2

R/W

A393

35

4

0.01 3600.00s

*100

3rd Deceleration time 2

No

R/WOS