3 pzd word 3-10 – Hitachi SJ-PB(T) User Manual

Page 20

Advertising
background image

CHAPTER5 OPERATING

16

5.3.3 PZD word 3-10

In PZD word 3-10 the user can determine which inverter parameters that should be transferred to/from the
inverter every bus-cycle.
With some of the PPO types (PPO2, 4, 5) it is possible to read and write parameters cyclically. Parameter write
values are placed in the PZD’s 3-10 transferred from the master to the inverter. Parameter read values are
placed in the PZD’s 3-10 transferred from the inverter to the master. However, the meaning of the data
transferred in PZD3-10 must be defined in some way so that it can be determined what parameters that shall be
written, and also so that the data transferred from the inverter can be connected with the correct parameter.
Parameter 915 and 916 are used to determine what parameters that shall be written (915) and read (916)
cyclically (parameter number as specified below, for examples of how to assign these refer to chapter 5.4.2 and
5.4.3).

Assignment of PZD write word 3-10 (PLC -> Inverter) with parameter 915:

915, sub-index 1 = Parameter number for parameter transferred in PZD3

915, sub-index 2 = Parameter number for parameter transferred in PZD4

915, sub-index 3 = Parameter number for parameter transferred in PZD5

915, sub-index 4 = Parameter number for parameter transferred in PZD6

915, sub-index 5 = Parameter number for parameter transferred in PZD7

915, sub-index 6 = Parameter number for parameter transferred in PZD8

915, sub-index 7 = Parameter number for parameter transferred in PZD9

915, sub-index 8 = Parameter number for parameter transferred in PZD10

Assignment of PZD read word 3-10 (Inverter ->PLC) with parameter 916:

916, sub-index 1 = Parameter number for parameter transferred in PZD3

916, sub-index 2 = Parameter number for parameter transferred in PZD4

916, sub-index 3 = Parameter number for parameter transferred in PZD5

916, sub-index 4 = Parameter number for parameter transferred in PZD6

916, sub-index 5 = Parameter number for parameter transferred in PZD7

916, sub-index 6 = Parameter number for parameter transferred in PZD8

916, sub-index 7 = Parameter number for parameter transferred in PZD9

916, sub-index 8 = Parameter number for parameter transferred in PZD10

Please Note:

1. PZD words 3-6 are enabled if PPO 2 or 4 is selected. PZD words 3-10 are enabled with PPO5.

2. Parameter numbers are within the range 1-418. See chapter 5 for an index of the inverter parameter numbers.

If a parameter number is set to 0, the actual PZD word will be ignored.

3. Only parameters that are of size two bytes or less can be assigned as PZD objects.