CHAPTER 6 COUNTERMEASURE FOR ABNORMALY

21

6.1 Trip display

When the inverter is in a tripped state, the inverter displays an error code (See table below). The trip history
monitor (d081 to d086) also displays the same error code as the inverter.

6.2 Protection function list

The table below describes an error code for protecting the inverter and the motor.
Error Display in the table below, X is 6 (Error for option slot 1) or 7 (Error for option slot 2).

No.

Function

Error
Display

Action

1

Profibus communication
error

EX0

This error is displayed, when disconnection occurred, while
the inverter is operating with Profibus.

2

Inverter communication
error

EX9

This error is displayed, when communication timeout occurs
between the inverter and the option board.

With regard to the other errors except table above, refer to Inverter instruction manual chapter 4 Explanation
of function.

6.3 Countermeasure for a trip state

The table below only corresponds to additional trip codes, with regard to the other countermeasures refer to
Inverter instruction manual chapter 4 Explanation of function.

Trip
code

Name of trip

Cause

Conformation

Countermeasure

Defective connector for
signal cable causes
connection fail.

Check the area of
connection.

Improve the connection and then
reset the power supply.

Terminating resistor is
not connected.

Check the Connection

Connect the terminating Resistor
and then reset the power supply

EX0

Profibus
Communication
error

Wiring distance does not
much with baudrate.

Check the
wiring distance

Adjust the setting to the matching
Baudrate or adjust wiring distance

EX9

Inverter
communication
error

Option board is
removed.

Check as mentioned left

Mount the option board again and
then secure it with screws.

6.4 LED display and Countermeasure

Following states are indicated by three LED's.

LED

Color

Function

Countermeasure

Green

Fieldbus is on-line.

-

Fieldbus

On/Off

Red

Fieldbus is off-line.

Confirm connection fails of connector.

Flash Red 1Hz

Configuration error.

Confirm setting data and send correct data.

Flash Red 2Hz

User configuration data error.

Confirm system setting and adjust adequate.

Fieldbus

diagnosis

Flash Red 4Hz

VPC3+ initialization failed.

Need to change the SJ-PB.

Green

Serial channel status OK.

-

Flash Red 1Hz

Serial communication error.

Confirm cable length and connection fails of
connector. And then adjust adequate.

Serial channel

status

Red

No serial communication.
(Or during initializing inverter
data. In this case, after
initializing, LED color returns to
green )

Confirm cable length and connection fails of
connector. And then adjust adequate.

Trip code

Inverter’s running condition of trip detected