Vent clearances and framing – Heatiator CB4842IR User Manual

Page 22

Advertising
background image

Heatilator • Caliber BV Series • 4040-262 • Rev M • 08/09

22

A. Pipe Clearances to Combustibles

Vent clearances are per vent manufacturer’s specifica-

tions. The vent MUST be Listed B-Vent pipe.

WARNING! Risk of Fire! MAINTAIN AIR space clearance

to vent.

DO NOT pack insulation or other combustibles:

• Between ceiling firestops

• Between wall shield firestops

• Around vent system
Failure to keep insulation or other material away from vent

pipe may cause over heating and fire.

8

Vent Clearances and Framing

B. Wall and Ceiling Penetration Framing

For a wall or ceiling penetration consult B-vent pipe

manufacturer’s instructions to provide adequate clear-

ances. Use same size framing materials as those used in

the wall or ceiling construction. Firestop spacers must

be used in wall and ceiling penetrations per the B-Vent

pipe manufacturer’s specifications and national, regional

and local codes.

Note: MUST terminate vertically.

C. Vertical Penetration Framing

WARNING! Fire Risk. DO NOT allow loose materials or

insulation to touch vent. Hearth & Home Technologies Inc.

requires the use of an attic shield.
The National Fuel Gas Code ANSI Z22. and NFPA 54

requires an attic shield constructed of 26 gauge minimum

metal that extends at least 2 in. (5 mm) above insulation.
Attic shields must meet specified clearance and be se-

cured in place.
Use B-vent manufacturer’s firestops to provide adequate

clearances.