Csdv series direct vent gas stove, Venting installation – Monessen Hearth CSDV40SLP User Manual

Page 14

Advertising
background image

14

58D6056

CSDV Series Direct Vent Gas Stove

Outside Corner

Inside Corner

Termination Clearances

Termination clearances for buildings with combustible and noncombustible exteriors.

G =

Combustible

6" (152 mm)

Noncombustible

2" (51 mm)

F =

Combustible

6" (152 mm)

Noncombustible

2" (51 mm)

G

Balcony -

with no side wall

M =
Combustible &
Noncombustible
12" (305 mm)

M

Balcony -

with perpendicular side wall

M = 24" (610 mm)
P = 20” (508 mm)

M

F

Alcove Applications*

C

D

C

E

V

V

Combustible &

Noncombustible

V

V

V

E

= Min. 6” (152 mm) for

non-vinyl sidewalls
Min. 12” (305 mm) for
vinyl sidewalls

O

= 8’ (2.4 m) Min.

O

P

Figure 12 -
Allowable
Venting

584-15

No.

of Caps

D

Min.

C

Max.

1

3’ (914 mm) 2 x D

Actual

2

6’ (1.8 m)

1 x D

Actual

3

9’ (2.7 m)

2/3 x D

Actual

4

12’ (3.7 m)

1/2 x D

Actual

D

Min.

= # of Termination caps x 3

C

Max.

= (2 / # termination caps) x D

Actual

*NOTE: Termination in an alcove space (spaces open only on one side and with an overhang) is permitted with the dimensions specified for vinyl or
non-vinyl siding and soffits. 1. There must be a 3’ (914 mm) minimum between termination caps. 2. All mechanical air intakes within 10’ (1 m) of a
termination cap must be a minimum of 3’ (914 mm) below the termination cap. 3. All gravity air intakes within 3’ (914 mm) of a termination cap must
be a minimum of 1’ (305 mm) below the termination cap.

VENTING INSTALLATION

  2
  0

4

6

8

10

12

14

16

18

20

22

24

26

28

30

32

34

36

38

40

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

HORIZONTAL RUN 20' MAX (6.1m)

VER

TICAL

 HEIGHT

 40' MAX (12.2m)

(MEASURED FROM ST

OVE 

T

OP) 

NOTE: Any vent configurations within
the shaded areas are acceptable.

Use Restrictor
Disk Above 
Dotted
Line 

Minimum Height from Stove Top 18" 

ST1136
venting graph

Actual Stove Height
CSDV20 = 23Z\x" (597 mm)
CSDV30 = 28Z\x" (724 mm)
CSDV40 = 30Z\x" (775 mm)

minimum Height from
Stove Top
CSDV20 = 18" (457 mm)
CSDV30 = 30" (762 mm)
CSDV40 = 30" (762 mm)

Figure 13 -
Acceptable Venting
Configurations