Fp1955 horizontal vent cap, Fp1956 vinyl siding standoff, Warning – Monessen Hearth CSDV40SLP User Manual

Page 16: Fp1957 install firestop, Horizontal termination configuration examples

Advertising
background image

16

58D6056

CSDV Series Direct Vent Gas Stove

VENTING INSTALLATION

9Z\x"

(241 mm)

9Z\x"

(241 mm)

Vent Opening for Combustible Walls

Framing Detail

Vent Opening for Noncombustible Wall

7Z\x"

(190 mm)

VO584-100

VO584-100
Vent Opening
2/99 djt

Figure 17 -
Locate Vent Opening on Wall

HOT

FP1955
horizontal vent cap

Vent Cap

Wood Screw

Apply Mastic to
All Four Sides

Figure 18 -
Install Horizontal Vent Cap

FP1955

HOT

FP1956
vinyl siding standoff

Apply Mastic to
All Four Sides

Cut Vinyl Siding
Away to Fit Standoff

Wood
Screw

Vent
Cap

Bolt

Nut

Standoff

FP1956

Figure 19 -
Install Vinyl Siding Standoff

W

ARNING

Do not recess vent termination into any
wall.
This will cause a fire hazard.

5. Slide the wall thimble over the vent pipe before con-

necting the horizontal run to the vent cap. Figure 20

6. Carefully move the stove with vent assembly attached

toward the wall and insert the vent pipe into the hori-
zontal termination. The pipe overlap should be a mini-
mum of 1Z\v" (32 mm). Apply silicone to the outer pipe
connection. Fasten all vent connections with screws
provided.

7. Slide the wall thimble against the interior wall surface

and attach with screws. Figure 20

FP1957
install firestop

Interior Wall
Surface

Decorative
Wall Thimble

Horizontal
Vent Pipe

Screw

Vent Cap
(Horizontal
Termination)

FP1957

Figure 20 -
Connect Vent Cap with
Horizontal Vent Pipe

HORIZONTAL TERmINATION
CONFIGURATION ExAmpLES

Figures 21 through 23 show different configurations for
venting and horizontal termination. Each figure includes a
chart with an example of horizontal maximum and vertical
minimum dimensions taken from the chart on Page 14.
NOTE: The horizontal run controls the mini-
mum vertical height (i.e. the longer the hori -
zontal run, the higher the termination will be).
Follow the chart on Page 14. All horizontal terminations
require a 1/4" (6 mm) rise per 12" (305 mm) of horizontal
run.