Section 8 − operating auxiliary equipment, 1. 120 volt and 240 volt receptacles – Miller Electric Big 40 CX User Manual

Page 38

Advertising
background image

OM-4427 Page 34

SECTION 8 − OPERATING AUXILIARY EQUIPMENT

8-1. 120 Volt And 240 Volt Receptacles

191 624-A

2

1

120 V 20 A AC GFCI

Receptacle GFCI1

2

240 V 30 A AC Twistlock

Receptacle RC1

Receptacles supply 60 Hz single-

phase power at weld/power speed.
If a ground fault is detected, GFCI

Reset button pops out and

receptacle does not work. Check

for faulty tools plugged in

receptacle. Press button to reset

GFCI1.

.

At least once a month, run en-
gine at weld/power speed and

press test button to verify GFCI

is working properly.

3

Circuit Breaker CB1

4

Circuit Breaker CB2

CB1 protects RC1 and the genera-

tor winding from overload. If CB1

opens, RC1 and GFCI1 do not

work. Place switch in On position to

reset breaker.
CB2 protects GFCI1 from overload.

If CB2 opens, GFCI1 does not

work. Press button to reset breaker.

.

If a circuit breaker continues to
open, contact Factory Autho-

rized Service Agent.

.

Generator power is not af-
fected by weld output.

Maximum output is 2.4 kVA/kW

from GFCI1 and 4 kVA/kW from

RC1. Maximum output from all re-

ceptacles is 4 kVA/kW.
EXAMPLE: If 13 A is drawn from

RC1, only 7 A is available at GFCI1:
(240 V x 13 A) + (120 V x 7 A) =

4.0 kVA/kW

1

3

4

Advertising
This manual is related to the following products: