9-8. Overload Protection

803 605

2

1

9

8

7

4

5

Y Stop engine.

.

When a circuit breaker or fuse
opens, it usually indicates a more se-

rious problem exists. Contact Facto-

ry Authorized Service Agent.

1

Fuse F1

2

Fuse F2

F1 and F2 protect the stator exciter wind-

ing from overload. If F1 opens, weld and

generator power is low or stops entirely.

If F2 opens, weld output is low or stops

entirely. 4 kVA/kW generator power is still

available.
3

Circuit Breaker CB4 (Not Shown)

4

Circuit Breaker CB5

(CC/CV Models Only)

5

Circuit Breaker CB6

(CC/CV Models Only)

6

Circuit Breaker CB10 (Not Shown)

7

Circuit Breaker CB11

8

Circuit Breaker CB12

9

Circuit Breaker CB13

10 Circuit Breaker CB14 (Not Shown)
CB4 protects the welding arc drive (dig)

circuit. If CB4 opens, electrode may stick

to the workpiece more frequently during

low voltage (short arc length) conditions.

CB4 automatically resets when the fault

is corrected.
CB5 protects the 24 volt ac output to re-

mote receptacle RC14, and 24 volt output

to field current regulator board PC1 (CC/

CV models only). If CB5 opens, weld out-

put and 24 volt output to RC14 stops. On

units with optional three-phase genera-

tor, generator power output at receptacle

RC5 also stops if CB5 opens.
CB6 protects the 115 volt ac output to re-

mote receptacle RC14 (CC/CV models

only). If CB6 opens, 115 volt output to

RC14 stops.
CB10 protects the engine battery circuit.

If CB10 opens, the engine will not crank.

CB10 automatically resets when the fault

is corrected.
CB11 protects the weld control circuit. On

CC models, if CB11 opens the max OCV

circuit does not work and open circuit

voltage is variable at all times (see max

OCV note under Weld Controls in Section

6-2). If CB11 opens on CV models, weld

output stops (generator power is still

available).
CB12 protects the field flashing circuit. If

CB12 opens, the generator may not ex-

cite at start-up and weld and generator

power output may not be available.
CB13 protects the engine control circuit.

If CB13 opens, the engine does not

crank.
CB14 protects throttle solenoid TS1 on

units with auto idle option. If CB14 opens,

the engine does not run at idle speed.

CB14 automatically resets when the fault

is corrected.
Press button to reset breaker.