8-3. Optional Generator Power Receptacles

2

1

120 V 20 A AC GFCI

Receptacle GFCI1

2

240 V 16 A AC European

Receptacle RC1

3

240 V 15 A AC Australian

Receptacle RC1

4

240 V 15 A AC South African

Receptacle RC1

Receptacles supply 60 Hz single-

phase power at weld/power speed.
If a ground fault is detected, the

GFCI Reset button pops out and

the receptacle does not work.

Check for faulty tools plugged in

receptacle. Press button to reset

GFCI1.

.

At least once a month, run en-
gine at weld/power speed and

press test button to verify GFCI

is working properly.

5

Circuit Breaker CB2

6

Circuit Breaker CB3

CB2 protects GFCI1 from overload.

If CB2 opens, GFCI1 does not

work. Press button to reset breaker.
CB3 protects RC1 from overload. If

CB3 opens, RC1 does not work.

Press button to reset breaker.

.

If a circuit breaker continues to
open, contact Factory Autho-

rized Service Agent.

.

Generator power is not af-
fected by weld output.

Maximum output is 2.4 kVA/kW

from GFCI1 and 4 kVA/kW from

RC1. Maximum output from all re-

ceptacles is 4 kVA/kW.
EXAMPLE: If 13 A is drawn from

RC1, only 7 A is available at GFCI1:
(240 V x 13 A) + (120 V x 7 A) =

4.0 kVA/kW

1

5

191 624

3

1

4

1

6

5

6

5

6

European Receptacle

Australian Receptacle

South African Receptacle