Chapter 2. Installation

Unpacking and Inspection

13

Mounting Kits

13

Configuration 14

Select Internal IF Loop

14

Connect External Cables

14

Connector Description

14

2.1 U

NPACKING AND

I

NSPECTION

Inspect shipping containers for damage. If shipping containers are damaged, keep them
until the contents of the shipment have been carefully inspected and checked for normal
operation.

Remove the packing list from the outside of the shipping carton. Open the carton and
remove the contents, checking the contents against the packing list. Verify completeness
of the shipment and that the unit functions correctly. If damage is evident, contact the
carrier and Comtech EF Data immediately and submit a damage report. Keep all shipping
materials for the carrier's inspection.

If the unit needs to be returned to Comtech EF Data, please use the original shipping
container.

2.2 M

OUNTING

K

ITS

If the CiM-550 is to be mounted in a rack, ensure that there is adequate clearance for
ventilation. The CiM-550 does not include a cooling fan, so care must be taken that too
many units are not mounted on top of each other. The limit is four units, and then a blank
1U panel must be inserted to allow sufficient airflow around the units. In rack systems
where there is high heat dissipation, forced air cooling must be provided by top or bottom
mounted fans or blowers. Under no circumstance should the highest internal rack
temperature be allowed to exceed 50° C.