7.7

Overload Protection

Y Stop engine. If checking

fuse, disconnect battery

negative (−) cable.

.

Press button to reset circuit
breaker. If fuse or breaker

continues to open, contact

Factory Authorized Service

Agent.

Weld And Auxiliary Power

Circuits
1

Fuse F2

F2 protects battery excitation

circuit. If F2 opens, weld and auxil-

iary output stops.
2

Fuse F3

F3 protects generator excitation

circuit. If F3 opens, weld and auxil-

iary power output is low.
Replace any open fuses. Reinstall

panel before operating unit.
Remote Control Circuit
3

Circuit Breaker CB5

CB5 protects 24 volt ac output to

Remote 14 receptacle RC1. If CB5

opens, RC1 24 volt output stops.
Engine Control Circuit
4

Circuit Breakers CB6, CB7,

CB8, And CB9

CB6 protects fuel solenoid circuit. If

CB6 opens, the engine does not

start.
CB7 protects throttle solenoid

circuit. If CB7 opens, the engine

does not run at weld/power speed.
CB8 protects Engine Control

switch and wiring harness. If CB8

opens, the engine does not crank.
CB9 protects optional glow plug

system. If CB9 opens, the glow plug

does not work.