3 run-in procedure using resistance grid – Miller Electric Metro 250D User Manual

Page 42

Advertising
background image

38

OM-402

9.3

Run-In Procedure Using Resistance Grid

S-0684

Y Stop engine.
Y Do not touch hot exhaust

pipe, engine parts, or load

bank/ grid.

Y Keep exhaust and pipe away

from flammables.

1

Resistance Grid

Use grid sized for generator rated

output.
Turn Off grid.
2

Welding Generator

Set Amperage control at min.
3

Weld Cables

Connect grid to generator weld

output terminals using proper size

weld cables with correct connec-

tors (polarity is not important).
4

Voltmeter

5

Clamp-On Ammeter

Connect voltmeter and ammeter as

shown, if not provided on generator.
Start engine and run for several

minutes.
Set grid switches and then adjust

Amperage control so load and out-

put are 180 A.
Check generator and meters after

first five minutes then every fifteen

minutes to be sure generator is

loaded properly.

.

Check oil level frequently dur-
ing run-in; add oil if needed.

After one hour (minimum), place

Amperage control in minimum posi-

tion, then shut down grid to remove

load. Run engine several minutes

at no load.
Y Stop engine and let cool.
6

Engine Exhaust Pipe

Repeat procedure if wetstacking is

present.

1

3

2

5

6

+

4