Table 5. Temperature and humidity requirements for storage subsystem when in storage or in
transit

Condition

Parameter

Requirement

Temperature

Storage range

-10° - 65° C (14° - 149° F)

Maximum rate of change

15° C (27° F) per hour

Transit range

-40° C to 65° C (-40° F to
149° F)

Maximum rate of change

20° C (36° F) per hour

Relative humidity (no
condensation)

Storage range

8% to 90%

Transit range

5% to 95%

Maximum dew point

26° C (79° F)

Maximum gradient

10% per hour

Table 6. Temperature and humidity requirements for storage subsystem in a typical
Information Technology (IT) or office environment

Condition

Parameter

Requirement

Temperature

Operating range

10° - 35° C (50° - 95° F)

Maximum rate of change

10° C (18° F) per hour

Relative humidity (no
condensation)

Operating range

8% to 80%

Altitude

Table 7 lists the acceptable altitudes for operating, storing, and shipping the
DS5020.

Table 7. DS5020 altitude ranges

Environment

Altitude

Operating

30.5 m (100 ft.) below sea level to 3000 m
(9842 ft.) above sea level

Storage

30.5 m (100 ft.) below sea level to 3000 m
(9842 ft.) above sea level

Transit

30.5 m (100 ft.) below sea level to 12,000 m
(40,000 ft.) above sea level

Airflow and heat dissipation

Figure 10 on page 22 shows the intended airflow for the DS5020. Allow at least 30
inches in front of the storage subsystem and at least 24 inches behind the storage
subsystem for service clearance, proper ventilation, and heat dissipation.