Cornelius SID650A/80 User Manual

Page 25

Advertising
background image

22

91704

YES

NO

2.B COMPRESSOR INOPERATIVE

IS

LINE VOLTAGE

WITHIN 10%

OF NAMEPLATE

VOLTAGE?

CHECK VOLTAGE

PROBLEMS IN 1 .

IS

THERMAL

PROTECTOR

OPEN?

IS

CONTACTOR

PULLED

IN?

IS

COMPRESSOR

BODY

COLD?

REPLACE

THERMAL

PROTECTOR.

IS

120V.

PRESENT AT

CONTACTOR

COIL

TERMINAL?

REPLACE CONTACTOR.

NO

YES

NO

YES

YES

NO

YES

NO

1. CHECK FOR LOOSE OR BROKEN WIRING

CONNECTION IN COMPRESSOR POWER

CIRCUIT.

2. CHECK CONTACTOR.
3. CHECK STARTING RELAY.
4. CHECK CAPACITOR(S).
5. CHECK COMPRESSOR MOTOR.

1. CHECK FOR LOOSE OR BROKEN

WIRING CONNECTION IN CONTROL

CIRCUIT.

2. GO TO 2.A