Using the Keypad with Settings and

Parameters

To use the keypad when working with Setpoints, System and

Advanced Settings, Checkout tests, and Alarms:

• Navigate to the desired menu.
• Press the  button (Enter) to display the first item in the

currently displayed menu.

• Use the

and

buttons to scroll to the desired

parameter.

• Press the  button (Enter) to display the value of the

currently displayed item.

• Press the

button to increase (change) the displayed

parameter value.

a

• Press the

button to decrease (change) the displayed

parameter value.

a

• Press the  button to accept the displayed value and store

it in non-volatile RAM.

• CHANGE STORED displays.
• Press the  button (Enter) to return to the current menu

parameter.

• Press the

button (MenuUp/Exit) to return to the

previous menu.

a

When values are displayed, pressing and holding the

or

button causes the display to automatically

increment.

Menu Structure

Table 4 on page 10 illustrates the complete hierarchy of

menus and parameters for the JADE™ Economizer system.

The Menus in display order are:

• STATUS

• SETPOINTS

• SYSTEM SETUP

• ADVANCED SETUP

• CHECKOUT

• ALARMS

IMPORTANT

Table 4 on page 10 illustrates the complete hierarchy.
Your menu parameters will be different depending on
your configuration.

For example if you do not have a DCV (CO

2

) sensor,

then none of the DCV parameters appear and only
MIN POS will display. If you have a CO2 sensor, the
DCV MIN and DCV MAX will appear AND if you have
2 speed fan DCV MIN (high and low speed) and DCV
MAX (high and low speed will appear).

SETUP AND CONFIGURATION

Before being placed into service, the JADE™ Economizer

module must be setup and configured for the installed system.

IMPORTANT

During setup, the Economizer module is live at all
times.

The setup process uses a hierarchical menu structure that is

easy to use. You press the

and

arrow buttons to move

forward and backward through the menus and press the 

button to select and confirm setup item changes.

Table 4. Menu Structure

a

.

Menu

Parameter

Parameter

Default

Value

Parameter

Range and

Increment

b

Notes

STATUS

ECON AVAIL

NO

YES/NO

YES = economizing available; the system can use Outdoor Air for

free cooling when required.

ECONOMIZING

NO

YES/NO

YES = Outdoor Air being used for 1

st

stage cooling.

OCCUPIED

NO

YES/NO

YES = OCC signal received from space thermostat or unitary

controller.

YES = 24 Vac on terminal OCC

No = 0 Vac on terminal OCC.

HEAT PUMP

n/a

c

COOL

HEAT

Displays COOL or HEAT when system is set to heat pump (non-

conventional)

COOL Y1-IN

OFF

ON/OFF

Y1-I signal from space thermostat or unitary controller for

cooling stage 1.

ON = 24 Vac on term Y1-I

OFF = 0 Vac on term Y1-I

COOL Y1-OUT

OFF

ON/OFF

Cool Stage 1 Relay Output to mechanical cooling (Y1-OUT

terminal).