Sequence of operation – Jade Range W7220 User Manual

Page 16

Advertising
background image

JADE

ECONOMIZER MODULE

62-0331—11

16

SEQUENCE OF OPERATION

Table 5. Dry Bulb Operation No DCV (CO2 sensor) - 1 Speed Fan.

a

With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if

the call for Y1-I and Y2-I have not been satisfied.

Table 6. Dry Bulb Operation With DCV (CO2 sensor) - 1 Speed Fan.

a

With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if

the call for Y1-I and Y2-I have not been satisfied.

DCV

OA Good to

economize?

Y1-I

Y2-I

FAN SPD

Y1-O

Y2-O

Occupied

Unoccupied

None

No

Off

Off

High

0-v/Off

0-v/Off

MIN POS

Closed

On

Off

High

24-v/On

0-v/Off

MIN POS

Closed

On

On

High

24-v/On

24-v/On

MIN POS

Closed

None

Yes

Off

Off

High

0-v/Off

0-v/Off

MIN POS

Closed

On

Off

High

0-v/Off

0-v/Off

MIN POS to Full-

Open

Closed to Full-Open

On

On

High

24-v/On

0-v/Off

a

MIN POS to Full-

Open

Closed to Full-Open

DCV

OA Good to

economize?

Y1-I

Y2-I

FAN SPD

Y1-O

Y2-O

Occupied

Unoccupied

Below CO2

set

No

Off

Off

High

0-v/Off

0-v/Off

VENTMIN

Closed

On

Off

High

24-v/On

0-v/Off

VENTMIN

Closed

On

On

High

24-v/On

24-v/On

VENTMIN

Closed

Yes

Off

Off

High

0-v/Off

0-v/Off

VENTMIN

Closed

On

Off

High

0-v/Off

0-v/Off

VENTMIN to Full-

Open

Closed to Full-Open

On

On

High

24-v/On

0-v/Off

a

VENTMIN to Full-

Open

Closed to Full-Open

Above CO2

set

No

Off

Off

High

0-v/Off

0-v/Off

VENTMIN to

VENTMAX

Closed

On

Off

High

24-v/On

0-v/Off

VENTMIN to

VENTMAX

Closed

On

On

High

24-v/On

24-v/On

VENTMIN to

VENTMAX

Closed

Yes

Off

Off

High

0-v/Off

0-v/Off

VENTMIN to

VENTMAX

Closed

On

Off

High

0-v/Off

0-v/Off

VENTMIN to Full-

Open

Closed to Full-Open

On

On

High

24-v/On

0-v/Off

a

VENTMIN to Full-

Open

Closed to Full-Open