Troubleshooting, Alarms – Jade Range W7220 User Manual

Page 19

Advertising
background image

JADE

ECONOMIZER MODULE

19

62-0331—11

Table 12. Enthalpy Operation With DCV (CO2 sensor) - 2 Speed Fan.

a

With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if

the call for Y1-I and Y2-I have not been satisfied.

b

With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to

satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage

mechanical cooling is enabled.

TROUBLESHOOTING

Alarms

The Economizer module provides alarm messages that

display on the 2-line LCD.

NOTE: Upon power up, the module waits 60 minutes

before checking for alarms. This allows time for

all the configured devices (e.g. sensors, actua-

tor) to become operational. The exception is the

MA sensor which will alarm immediately. If one or

more alarms are present and there has been no

keypad activity for at least 5 minutes, the Alarms

menu displays and cycles through the active

alarms.

You can also navigate to the Alarms menu at any time.

DCV

OA Good to

economize?

Y1-I

Y2-I

FAN SPD

Y1-O

Y2-O

Occupied

Unoccupied

Below set

No

Off

Off

Low

0-v/Off

0-v/Off

VENTMIN L

Closed

On

Off

Low

24-v/On

0-v/Off

VENTMIN L

Closed

On

On

High

24-v/On

24-v/On

VENTMIN H

Closed

Yes

Off

Off

Low

0-v/Off

0-v/Off

VENTMIN L

Closed

On

Off

Low

0-v/Off

0-v/Off

VENTMIN L to Full-

Open

Closed to Full-Open

On

On

High

24-v/On

0-v/Off

a

VENTMIN H to Full-

Open

Closed to Full-Open

Above set

No

Off

Off

Low

0-v/Off

0-v/Off

VENTMIN L to

VENTMAX

Closed

On

Off

Low

24-v/On

0-v/Off

VENTMIN L to

VENTMAX

Closed

On

On

High

24-v/On

24-v/On

VENTMIN H to

VENTMAX

Closed

Yes

Off

Off

Low

0-v/Off

0-v/Off

VENTMIN L to

VENTMAX

Closed

On

Off

Low

0-v/Off

0-v/Off

VENTMIN L to Full-

Open

Closed to Full-Open

On

On

High

DELAY

b

24-v/On

0-v/Off

a

VENTMIN H to Full-

Open

Closed to Full-Open

Table 13. Alarms Menu.

Menu

Alarm

ALARMS(_)

MA T SENS ERR
CO2 SENS ERR
OA T SENS ERR
DA ENTHL ERR

SYS ALARM

a

a

When AUX1 O is set to SYS and there is any alarm (e.g.,

failed sensors, etc.), the AUX1 O terminal has 24 Vac out

and the LCD displays the ALARM.

b

This alarm is only displayed when a communicating actuator

is used. (ex: MS3105AJ)

ACT Over Voltage

b

ACT Under Voltage

b

ACT Stalled

b

NOTES:

1.

The Alarms menu displays only when alarm(s)

are active and includes the number of active

alarms in parenthesis ().

2.

The alarms listed are a few examples. Additional

alarms display depending on the parameter set-

tings and configuration.