ECONOMIZER MODULE

9

62-0331—11

Fig. 8. Single Enthalpy curves and boundaries.

Power Up

After the module is mounted and wired, apply power.

Power Up Delay

Upon power up (or after a power outage or brownout), the

W7220 controller module begins a 5 minute power up delay

before enabling mechanical cooling.

Initial Menu Display

On initial start up,

Honeywell displays on the first line and

Economizer W7220 on the second line. After a brief pause,

the revision of the software appears on the first line and the

second line will be blank. After another brief moment the

screen will display W7220 on the first line and STATUS on the

second line. Refer to table 3 for menu structure.

Power Loss (Outage or Brownout)

All setpoints and advanced settings are restored

a

after any

power loss or interruption.

NOTE: If power goes below 18 Vac, the W7220 controller

module assumes a power loss and the 5 minute

power up delay will become functional when

power returns above 18 Vac.

Using the Keypad with Menus

To use the keypad when working with menus:

• Press the

button to move to the previous menu.

• Press the

button to move to the next menu.

• Press the  button (Enter) to display the first item in the

currently displayed menu.

• Press the

button (Menu up) to exit a menu’s item and

return to the list of menus.

ECONOMIZING

AVAILABLE

NOT AVAILABLE

TEMPERATURE

ABSOLUTE HUMIDITY

RA

TEMP

RA

HU

M (

%R

H)

ENTHALPY

ES4

ES3

ES2

ES1

HL

P2 (T,RH)

DUAL ENTHALPY

HIGH LIMIT

SINGLE ENTHALPY

ES5

P1

(T,RH)

M32286

Table 3. Single Enthalpy and Dual Enthalpy High Limit Curves.

Enthalpy

Curve

Temp.

Dry-Bulb (°F)

Temp.

Dewpoint (°F)

Enthalpy

(btu/lb/da)

Point P1

Point P2

Temp. °F

Humidity %RH

Temp. °F

Humidity %RH

ES1

80.0

60.0

28.0

80.0

36.8

66.3

80.1

ES2

75.0

57.0

26.0

75.0

39.6

63.3

80.0

ES3

70.0

54.0

24.0

70.0

42.3

59.7

81.4

ES4

65.0

51.0

22.0

65.0

44.8

55.7

84.2

ES5

60.0

48.0

20.0

60.0

46.9

51.3

88.5

HL

86.0

66.0

32.4

86.0

38.9

72.4

80.3

a

All settings are stored in non-volatile flash memory.