Jade Range W7220 User Manual

Page 18

Advertising
background image

JADE

ECONOMIZER MODULE

62-0331—11

18

Table 10. Dry Bulb Operation With DCV (CO2 sensor) - 2 Speed Fan.

a

With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if

the call for Y1-I and Y2-I have not been satisfied.

b

With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to

satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage

mechanical cooling is enabled.

Table 11. Enthalpy Operation No DCV (CO2 sensor) - 2 Speed Fan.

a

With stage 3 delay (STG3 DLY) in Advanced setup menu can turn on 2nd stage of mechanical cooling Y2 –O after the delay if

the call for Y1-I and Y2-I have not been satisfied.

b

With 2SP FAN DELAY (Advanced Setup Menu) when in the economizing mode there is a delay for the high speed fan to try to

satisfy the call for second stage cooling by turning on the fan to high and opening the OA damper 100% before the first stage

mechanical cooling is enabled.

DCV

OA Good to

economize?

Y1-I

Y2-I

FAN SPD

Y1-O

Y2-O

Occupied

Unoccupied

Below set

No

Off

Off

Low

0-v/Off

0-v/Off

VENTMIN L

Closed

On

Off

Low

24-v/On

0-v/Off

VENTMIN L

Closed

On

On

High

24-v/On

24-v/On

VENTMIN H

Closed

Yes

Off

Off

Low

0-v/Off

0-v/Off

VENTMIN L

Closed

On

Off

Low

0-v/Off

0-v/Off

VENTMIN L to Full-

Open

Closed to Full-Open

On

On

High

24-v/On

0-v/Off

a

VENTMIN H to Full-

Open

Closed to Full-Open

Above set

No

Off

Off

Low

0-v/Off

0-v/Off

VENTMIN L to

VENTMAX

Closed

On

Off

Low

24-v/On

0-v/Off

VENTMIN L to

VENTMAX

Closed

On

On

High

24-v/On

24-v/On

VENTMIN H to

VENTMAX

Closed

Yes

Off

Off

Low

0-v/Off

0-v/Off

VENTMIN L to

VENTMAX

Closed

On

Off

Low

0-v/Off

0-v/Off

VENTMIN L to Full-

Open

Closed to Full-Open

On

On

High

DELAY

b

24-v/On

0-v/Off

a

VENTMIN H to Full-

Open

Closed to Full-Open

DCV

OA Good to

economize?

Y1-I

Y2-I

FAN SPD

Y1-O

Y2-O

Occupied

Unoccupied

NO CO2

SENSOR

No

Off

Off

Low

0-v/Off

0-v/Off

MIN POS L

Closed

On

Off

Low

24-v/On

0-v/Off

MIN POS L

Closed

On

On

High

24-v/On

24-v/On

MIN POS H

Closed

Yes

Off

Off

Low

0-v/Off

0-v/Off

MIN POS L

Closed

On

Off

Low

0-v/Off

0-v/Off

MIN POS L to Full-

Open

Closed to Full-Open

On

On

High

DELAY

b

24-v/On

0-v/Off

a

MIN POS H to Full-

Open

Closed to Full-Open