JADE

ECONOMIZER MODULE

11

62-0331—11

STATUS

CONTINUED

COOL Y2-IN

OFF

ON/OFF

Y2-I signal from space thermostat or unitary controller for

second stage cooling.

ON = 24 Vac on term Y2-I

OFF = 0 Vac on term Y2-I

COOL Y2-OUT

OFF

ON/OFF

Cool Stage 2 Relay Output to mechanical cooling (Y2-OUT

terminal).

MA TEMP

_ _._ ºF

-40 to 150 ºF

Displays value of measured mixed air from MAT sensor.

Displays --.- if not connected, short, or out- of-range.

DA TEMP

_ _._ ºF

-40 to 150 ºF

Displays when Discharge Air Sylk Bus sensor is connected and

displays measured discharge air temperature.

Displays --.-°F if sensor sends invalid value, if not connected,

short or out-of-range.

OA TEMP

_ _._ ºF

-40 to 140 ºF

Displays measured value of outdoor air temperature.

Displays --°F if sensor sends invalid value, if not connected,

short or out-of-range.

OA HUM

_ _ %

0 to 100%

Displays measured value of outdoor humidity from QA Sylkbus

sensor. Displays --% if not connected, short, or out- of-range.

RA TEMP

_ _._ ºF

0 to 140 ºF

Displays measured value of return air temperature from RA

sensor. Displays --°F if sensor sends invalid value, if not

connected, short or out-of-range.

RA HUM

_ _ %

0 to 100%

Displays measured value of return air humidity from RA Sylkbus

sensor. Displays --% if sensor sends invalid value, if not

connected, short or out-of-range.

IN CO2

_ _ _ ppm 0 to 2000 ppm

Displays value of measured CO2 from CO2 sensor. Invalid if not

connected, short or out-of-range. May be adjusted in Advanced

menu by Zero offset and Span

DCV STATUS

n/a

ON/OFF

Displays ON if above setpoint and OFF if below setpoint, and

ONLY if a CO2 sensor is connected.

DAMPER OUT

2.0V

2.0 to 10.0 V

Displays output voltage or position to the damper actuator.

e

ACT POS

n/a

0 to 100%

Displays actual position of actuator.

ACT COUNT

n/a

1 to 65,535

Displays number of times actuator has cycled. 1 Cycle equals

the sum of 180° of movement in any direction.

ACTUATOR

n/a

OK/Alarm (on

Alarm menu)

Displays Error if voltage or torque is below actuator range

EXH1 OUT

OFF

ON/OFF

Output of EXH1 terminal.

ON = 24 Vac Output; OFF = No Output.

EXH2 OUT

OFF

ON/OFF

Output of AUX1 O terminal Displays ON when damper position

reaches programmed percentage setpoint

ON = 24 Vac Output, OFF = No Output; displays only if AUX1 O =

EXH2

ERV

OFF

ON/OFF

Output of AUX1 O terminal, ON = 24 Vac Output, OFF = No

Output; displays only if AUX1 O = ERV

MECH COOL ON

0

0, 1, or 2

Displays number of mechanical cooling stages that are active.

FAN SPEED

n/a

LOW or HIGH

Displays speed of fan on a 2-speed fan unit

W (HEAT IN)

n/a

ON/OFF

Displays status of heat on a 2-speed fan unit.

Table 4. Menu Structure

a

. (Continued)

Menu

Parameter

Parameter

Default

Value

Parameter

Range and

Increment

b

Notes