JADE

ECONOMIZER MODULE

62-0331—11

14

ADVANCED

SETUP

MA LO SET

45ºF

35 to 55 ºF;

increment by 1º

Temp to activate Freeze Protection (close damper or modulate to

MIN POS if temp falls below set value)

FREEZE POS

CLO

CLO

MIN

Damper position when freeze protection is active (closed or MIN

POS).

CO2 ZERO

0ppm

0 to 500 ppm;

increment by 10

CO2 ppm level to match CO2 sensor start level.

CO2 SPAN

2000ppm

1000 to 3000

ppm;

increment by 50

CO2 ppm span to match CO2 sensor; e.g.; 500-1500 sensor

output would be 500 CO2 zero and 1000 CO2 span.

STG3 DLY

2.0h

0 min, 5 min, 15

min, then 15

min intervals.

Up to 4h or OFF

Delay after stage 2 for cool has been active. Turns on 2nd stage

of mechanical cooling when economizer is 1st stage call and

mechanical cooling is 2nd stage call. Allows three stages of

cooling, 1 economizer and 2 mechanical.

OFF = no Stage 3 cooling.

SD DMPR POS

CLO

CLO

OPN

Indicates shutdown signal from space thermostat or unitary

controller. When controller receives 24 Vac input on the SD

terminal in conventional mode, the OA damper will open if

programmed for OPN and OA damper will close if programmed

for CLO. All other controls, e.g., Y1-O, Y2-O, EXH1, etc. will shut

off.

DCVCAL ENA

MAN

MAN (manual)

AUTO

Turns on the DCV automatic control of the dampers. Resets

ventilation based on the RA, OA and MA sensor conditions.

Requires all sensors (RA, OA, MA and CO2).

This operation is not operable with a 2-speed fan unit.

MAT T CAL

0.0 F°

+/-2.5F°

Allows for the operator to adjust for an out of calibration

temperature sensor

OA T CAL

0.0F°

+/-2.5F°

Allows for the operator to adjust for an out of calibration

temperature sensor

OA H CAL

0% RH

+/-10% RH

Allows for the operator to adjust for an out of calibration

humidity sensor

RA T CAL

0.0F°

+/-2.5F°

Allows for the operator to adjust for an out of calibration

temperature sensor

RA H CAL

0% RH

+/-10% RH

Allows for the operator to adjust for an out of calibration

humidity sensor

DA T CAL

0.0 F°

+/-2.5F°

Allows for the operator to adjust for an out of calibration

temperature sensor

2SP FAN DELAY

5 Minutes 0 to 20 minutes

in 1 minute

increments.

When in economizing mode this is the delay for the high speed

fan to try to satisfy the call for second stage cooling before the

first stage mechanical cooling is enabled.

Table 4. Menu Structure

a

. (Continued)

Menu

Parameter

Parameter

Default

Value

Parameter

Range and

Increment

b

Notes