Venting through a fireplace, Co-linear vent installation – Jotul GF 100 DV II User Manual

Page 11

Advertising
background image

11

GF 100 DV II Nordic QT

GF 200 DV II Lillehammer

Co-linear Vent Installation

This appliance may be vented through a masonry or
Class A prefabricated chimney using a Co-linear Flexible
Vent system approved for use with a solid-fuel burning
fireplace. When installed in the manner described below,
this system can improve the performance of the appli-
ance in cold climate situations, as well as simplify the
vent installation. See fig. 9.
These installation requirements must be followed:
1. Prior to the installation the chimney flue must be

thoroughly cleaned and inspected by a qualified
chimney service person.

2. In a masonry chimney, a fireclay liner must be present

the entire length of the chimney.

3. Prefabricated chimneys must be UL 103 or ULC S-629

listed and have a minimum INSIDE diameter of 6
inches, (150 mm).

4. No appliance can be installed into a chimney flue

serving any other appliance of any kind.

5. THE AIR INTAKE FLEX PIPE MUST EXTEND BEYOND THE

DAMPER AREA OF THE FIREPLACE. If the intake flex
duct does not extend the full length of the chimney
and connect to both the unit and the termination
cap, A METAL BLOCK OFF PLATE MUST BE CON-
STRUCTED AND INSTALLED ABOVE THE UNIT PRIOR TO
THE END OF THE INTAKE FLEX AND MUST COM-
PLETELY SEAL THE CHIMNEY FLUE FROM THE ROOM.

Consult with the local code authority having juris-

diction before proceeding with this type of installation.

Refer to the vent manufacturer’s instructions for

specific installation requirements.

WARNING: FAILURE TO POSITION THE PARTS AND

STOVE IN ACCORDANCE WITH THESE DIAGRAMS OR
FAILURE TO USE ONLY PARTS SPECIFICALLY APPROVED
FOR USE WITH THIS APPLIANCE, MAY RESULT IN PROP-
ERTY DAMAGE OR PERSONAL INJURY. BE SURE TO
MAINTAIN THE PROPER CLEARANCES TO COMBUSTIBLES
AS DEFINED IN THIS MANUAL AND IN THE INSTRUC-
TIONS PROVIDED WITH EACH VENT COMPONENT.

Figure 9.
Co-linear Adaptor installed through a masonry chimney.

Figure 10. Simpson Dura-Vent #923GCL Co-linear Adaptor.
GF 100 DV II:

A : 16 3/4”

B : 20 3/4”

GF 200 DV II:

A : 18”

B : 22”

Add 2 1/4” with Long Legs.
Subtract 1” with Plinth

Venting Through a Fireplace

A

B

Intake Air

Exhaust Gas

High Wind

Cap

Max.

Co-linear

Height 15 ft.

(10.66 m)

Min.

Co-linear

Height 8

ft.

(2.44 m)

Air Intake Flex

pipe must

extend above

the damper.

Sealed

Damper

Max.

Offset 24”

(609 mm)