Secure all joints tightly using appropriate tools

and sealing compounds (for propane units, be sure

to use compounds that are propane resistant).

Turn on gas supply and test for gas leaks using a

soapy water solution. Never use an open flame

to check for leaks.

Leak test:

· Mix a 50-50 solution of water and dish soap.

· Light appliance- see lighting instructions on

page 23 of this manual or on the stove’s rating

plate.

· Brush or spray all joints and connections with

the soapy water solution.

· If bubbles appear at any connection or seam

or a gas odor is detected, immediately turn

gas control knob to the OFF position.

Tighten or reconnect the leaking joint and retest

for any gas leaks.

GAS PRESSURE:

Correct gas pressure is essential for efficient and

safe operation of the Allagash gas stove. It is

important that the correct pressure is established

at the time of the installation.

Proper gas pressure provides a consistent flow of

gas to the appliance and is instrumental in

checking for gas leaks.The gas control valve on

the stove is equipped with pressure test points

for gauge connections. The gauge connections

are located on the front of the valve under the

On/Off/Pilot- knob. Gauge

connections are

identified by:

E for inlet or supply pressure (the amount of

gas coming to the valve.)

A for manifold pressure (the amount of gas that

is coming out of the valve to the burner.)

MAKING THE GAS CONNECTION:

NOTE: IF THE OPTIONAL FORCED BLOWER KIT

(

PART

# 129161) IS TO BE INSTALLED ON THE

STOVE AT THE TIME OF THE INSTALLATION

OR IN THE FUTURE, THE GAS SUPPLY LINE

SHOULD BE INSTALLED AS CLOSE TO THE

FLOOR AS POSSIBLE.

USE OF A 90° ELBOW DIRECTLY OFF THE VALVE

WILL ALLOW FOR PROPER CLEARANCE FOR

THE BLOWER.

The gas supply line connection is made to the valve

just inside the left rear leg. The Gas supply line

should be a minimum of 3/8" in diameter, or

the appropriate size to provide sufficient gas

pressure to the valve regardless of the input

setting.

The use of Flexible Gas Appliance Connectors is

acceptable in many areas in the U.S.; However,

Canadian methods vary depending on local code.

ALL INSTALLATIONS MUST COMPLY

WITH LOCAL CODE OR IN THE ABSENCE

OF LOCAL CODE, MUST COMPLY WITH

THE MOST RECENT EDITION OF THE

NATIONAL FUEL GAS CODE ANSI Z223.1/

NFPA 54 OR CAN-B149.

All codes require: a gas shut-off valve (gas cock)

and union, to be installed in the supply line, and

in the same room as the appliance. This allows

for the disconnection of the stove for servicing

and maintenance. See Figure 5.

Figure 5

T-handle gas cocks are required in Massachusetts

in compliance with code 248CMR.

E A

Pressure test point as located on the front of the valve.

12